Rumford Fireplace Emissions
TEST RESULTS

7/16/96


OMNI Environmental Services, Inc.
5465 SW Western Avenue, Suite M
Beaverton, OR 97005
503 643 3788

Prepared for:

Superior Clay Corp.
Buckley Rumford Co.


Test Results for the Buckley Rumford 30-Inch Fireplace

Executive Suammary

Beginning March 7, 1996, OMNI Environmental Services conducted emissions testing on the Buckley Rumford 30-inch fireplace to demonstrate compliance with Washington State UBC Standard 31-2(WAC 51-30-31200 section 3102.5.4). The fireplace was assembled and tested at OMNI's solid fuels testing laboratory in Beaverton, Oregon in two configurations; one with glass combustion chamber doors in place and closed, the other with the glass combustion chamber doors removed. No hearth grate or draft inducer was used in either configuration. The primary participants of the testing were Paul Tiegs, Senior Principal of OMNI and Jacob Tiegs, Laboratory Technician.

The results of the tests are summarized in Table 1. Particulate emission factor results are less than the Washington State standard of 7.3 g/kg.

Table 1. Particulate Emissions (30" Rumford)

ConfigurationOpen DoorClosed DoorAverage
g/kg Emissions Factor7.042.474.76
g/hr Emissions Rate31.465.0818.27


Test Results for the Buckley Rumford 48-Inch Fireplace

Executive Suammary

Beginning March 7, 1996, OMNI Environmental Services conducted emissions testing on the Buckley Rumford 48-inch fireplace to demonstrate compliance with Washington State UBC Standard 31-2(WAC 51-30-31200 section 3102.5.4). The fireplace was assembled and tested at OMNI's solid fuels testing laboratory in Beaverton, Oregon in two configurations; one with glass combustion chamber doors in place and closed, the other with the glass combustion chamber doors removed. No hearth grate or draft inducer was used in either configuration. The primary participants of the testing were Paul Tiegs, Senior Principal of OMNI and Jacob Tiegs, Laboratory Technician.

The results of the tests are summarized in Table 1. Particulate emission factor results are less than the Washington State standard of 7.3 g/kg.

Table 1. Particulate Emissions (48" Rumford)

ConfigurationOpen DoorClosed DoorAverage
g/kg Emissions Factor4.082.263.17
g/hr Emissions Rate42.327.1024.71



48" wide Rumford being tested at OMNI

Back to Latest Test Results

Official List: Certified Wood Stoves, Authorized Fireplaces and Other Solid Fuel Burning Devices

[Washington Certified Buckley Rumford Fireplaces]
[Certified Core] [Plan] [Instructions] [Building a Fire] [Registration & Warranty] [Test Results]

[Fireplace Emissions]

[The Rumford Store]
[Rumford Picture Gallery] [Specifications] [Plans & Instructions]
[Manufacturers] [Dealers] [Architects] [Builders] [Masons] [Sweeps]
[Associations] [Masonry Chimneys] [Masonry Heaters] [Training] [links] [search]
[Superior Clay Corporation]

Buckley Rumford Fireplace Home Page
Copyright 1996 - 2000 Jim Buckley
All rights reserved.